Aktek Endüstriyel

Contact Us

Ultrasonic Flowmeter TTFM 6.1

• For DN15…DN1200 Pipes
• Easy configuration with 5 buttons
• 4-20mA/0-5V, Flow proportional programmable Relay, outputs
• 26 Million point Data Logger
• LCD display with backlight
• Password protected
• Optional Modbus® RTU or HART

Ultrasonic Flowmeter TTFM 6.1

Measures with high accuracy the flow rate of relatively clean, unaerated liquids such as drinking water, raw water, wastewater, cooling water, deionized or reverse osmosis water, oils and chemicals in fully filled pipes.

Ultrasonic transducers are mounted on the outside of a pipe without stopping the flow. Flow is displayed on the large, backlit display along with total Flow, signal strength, relay status and other diagnostic values. Internal control relays are used as flow alarms or collectors.

Connect isolated 4-20mA output to PLCs or controllers. A 128 MB data logger is standard and has a capacity of 26 million data points. Optional MODBUS RTU via RS-485 is available for connection to automation systems. TTFM 6.1 operates on pipes made from a wide range of pipe diameters and materials. For example, carbon steel, stainless steel, ductile iron, concrete-lined ductile iron, cast iron, PVC, PVDF, fiberglass, copper, brass, aluminum  and  for gluing coated lined pipes including epoxy, rubber and Teflon.

TTFM 6.1 Transit Time Flow Meter is the “transit time” of ultrasonic sound pulses transmitted from one transducer to another. or “flight time” It works by measuring. Depending on the mounting configuration, the signal may pass the pipe one, two or four times.  To measure flow, transit time, upstream and  Ultrasonic signals traveling downstream are compared.

TTFM 6.1 Standard Features:

      • A pair of SE16B ultrasonic clamps  transducer – 2 ”… 48” (50 mm…. 1200 mm) for pipes
      • Optional: a pair of SE16A ultrasonic clamp-on transducers – 0.5 … 4 ″ (13 mm … 100 mm) for pipes
      • Sensor cables – with BNC connector 7.6 m triaxial double
      • Flow  range: ± 0.07 to 40 ft/sec (± 0.02 to 12 m/sec)
      • Installation – stainless steel transducer mounting brackets and clamps, alignment rod, and silicone acoustic coupler
      • Enclosure – waterproof, NEMA4X (IP66) polyester and polycarbonate
      • Display – white, backlit matrix
      • Collector – 14 digits
      • Programming – internal 5 keys
      • Çexit – isolated 4-20mA (1000 ohm)
      • 2 control relays – 5 amps, SPDT – flow proportional pulse  Programmable for output and/or flow alarm
      • Power entry – 100-240VAC 50/60Hz, maximum 10VA (Optional: 9-36VDC, maximum 10 Watt)
      • Data Logger – 128 MB storage capacity, 26 million data points, formattable as .csv or .lg2 for Greyline Logger Software
      • Surge protection and RFI filters – AC, sensor, 4-20mA
      • Plug-and-play options MODBUS RTU output and extra relay outputs

Application Areas:

  • Water & Wastewater
  • Drinking Water
  • River Water
  • Coolant
  • Demineralized Water
  • Crude Oil
  • Mineral Oil
  • Hydroelectric, Fire Extinguishing Stations
  • Food, Beverage Industry
  • Flow Balancing
  • Glycol solution
  • Hydraulic Oil
  • Diesel & Fuel Oil
  • Chemicals
  • Petrochemicals
  • Heating and Cooling Systems
  • Fire suppression systems

Purified water
Raw Water
Cooling Water
chemicals
Hydraulic oil
Low Conductivity Water
Water/Glycol Solutions
Diesel and Fuel oil

<p>The meter provides non-intrusive flow measurement, direction indicator, volume total and flow rate measurement and transmission in a fully filled pipe.</p>

<p>A. PERFORMANCE FEATURES</p>

<p>The ultrasonic flow meter shall have an accuracy of &plusmn;1% of the reading or &plusmn;0.015 ft/sec (&plusmn;0.0046 m/sec), whichever is greater.<br / >
Repeatability and linearity are &plusmn;0.25%.</p>

<p>&plusmn; In relatively clean liquids in full tubes with less than 2% solids or gas bubbles at flow velocities of 0.07% to 40 ft/sec (&plusmn; 0.02 to 12 m/sec). It works.</p>

<p>Carbon steel, stainless steel, ductile&nbsp;iron, concrete coated ductile&nbsp;iron, cast iron, PVC, PVDF, fiberglass, galvanized steel, copper, brass; and made of metal or plastic material that transmits ultrasonic sound, such as epoxy, rubber, and epoxy rubber teflon bonding. in coated pipes&nbsp; It works</p>

<p>The Ultrasonic Flowmeter is optimized and pre-programmed for the application when information such as pipe material, pipe diameter, wall thickness, liquid type, liquid temperature and maximum flow rate are given during the order.</p>

<p>B. CONVERTERS (FLOW SENSORS)</p>

<p>Flow meter, a&nbsp; Dual transmitter/receiver features clamp-on transducers.</p>

<p>Transducers, -40 &deg; C to 150°C It operates continuously at temperatures between C.</p>

<p>Transducer&nbsp;&ccedil;pair, inside&ccedil; Diameter 2" to 48" It is designed to be installed on pipes ranging from 50 mm to 1200 mm.</p>

<p>With BNC connector for connection between the electronic unit and transducers. &nbsp;7.6 m long &three;&ccedil; It has axis cables.</p>

<p>&Manufacturer's recommended acoustic coupler and&nbsp; Includes stainless steel mounting hardware with pipe clamps.</p>

<p>Shall include BNC sealing jackets for operation of transducers in wet or submerged conditions up to 10 psi (0.75 bar).</p>

<p>Converters, Class I, Division 2, Groups A, B, C &amp; It will be rated as non-stimulating for D locations.</p>

<p>C. ELECTRONICS</p>

<p>The electronic unit is housed in a waterproof and dustproof NEMA4X (IP 66) polyester and polycarbonate enclosure with a sealed shatterproof window and is suitable for wall mounting.</p> >

<p>Flowmeter electronics -20 &deg; C to 60°C C between -5 &deg; F to 140° It is designed to operate at temperatures between F. The transmitter circuit and calibration frequency standard are crystal controlled. Transmitter supply, power less than 10VA requiring 100-240VAC 50/60Hz.</p>

<p>Transmitter,&nbsp; Menu Includes a built-in 5-Key calibration system that can select operator parameters via visual prompts from the calibration system. Systems require calibration codes.&nbsp; external calibrators&nbsp; not accepted.</p>

<p>Insulated&nbsp; 4-20mA,&nbsp; With zero and full scale offset features, it can be programmed as flow proportional shall be flow proportional and isolated, with programmab. The maximum load resistance is 1000 ohms. For nearby lightning strikes&nbsp; High voltage protected.</p>

<p>Electronics filter noise to filter out electrical interference. Includes suppression circuit.</p>

<p>Electronics, white, showing flow rate, calibration units, relay states, signal strength, measured sound speed and 14-digit totalizer in user-selected engineering units. It has a backlit matrix LCD display.</p>

<p>Electronic, 5 amp SPDT has 2 control relays. Relays can be programmed for flow proportional&nbsp;pulse output or as flow alarms with separate ON/OFF setpoints.</p>

<p>Electronics display and collect forward and reverse flow.</p>

<p>The electronics must have a built-in data logger that can store up to 128 MB of data. Data can be downloaded to the flash drive via the type A USB port on the meter's front panel.</p>

<p>The electronics are modular and field replaceable with plug-in circuit boards. The device should automatically detect and load software menus for field installation options.</p>

<p>D. OPTIONAL FEATURES ADDING TO THE REQUIRED FEATURES:</p>

<p>Transformative couple, inside &ccedil;diameter 0.5&rdquo;to 4&rdquo; (15 mm to 10

Allows installation on pipes ranging from 0 mm. Includes BNC sealing jackets.</p>

<p>Transformative couple, inside &ccedil;diameter 0.5&rdquo;to 4&rdquo; It should allow installation on pipes ranging from 15 mm to 100 mm. Converter The cable must be connected directly to the transducer and stored to allow installation in wet environments. It is in IP67 protection class.</p>

<p>Transducer cables are three-dimensional with BNC transducer connections. axis&nbsp; It can be 15m or 30 meters long.</p>

<p>The transducer&nbsp;cable can be extended up to 150 m with the NEMA4X (IP 66) Junction Box.</p>

<p>Electronics, optionally MODBUS&reg; via RS-485 RTU or HART&nbsp; May include output. Data points for Modbus include flow rate, flow total, previous day's average flow rate, previous day's total volume, collector reset, relay output status, signal strength. ;, includes measured sound speed, runtime, transducer connection status, recorder status, and percentage of recording used. HART, 7.0&nbsp; version and DD&nbsp; files EMERSON&nbsp; Compatible with 475 HART Communicator.</p>

<p>Intrinsically Safe for Converters Class I, Division 1, Groups C and D Class II, Groups E, F and G; Class III; Type 4 dangerous places.</p>

<p>Electronics, temperature -20 &deg; It shall have a thermostatically controlled, AC-powered enclosure heater for condensation protection at temperatures below 100°C.</p>

<p>Electronics, less than 10 Watts of power. requires 9-32VDC power. It will have the entry.</p>

<p>Electronic, with 4 additions&nbsp; Can have (6 total) control relays, nominal 5 amp SPDT&nbsp; and as flow alarms or flow collector pulse&nbsp; programmable.</p>

Water

Wastewater

Food

Petrochemicals

Beverage

Oil and Gas

Power

Paper

×
Hello, I want to get information.