Sludge Finder 2
- Continuous single or dual-channel level control
- High frequency gives high-reliability long term
- Self-cleaning transducer removes the need for regular inspection
- SBR tank applications can be monitored
- Easy set-up via the drop-down menu on large clear display
- The unit can track two different echoes with one transducer
- Radio telemetry system – optional
The Sludge Finder 2 is used in thousands of applications worldwide to detect sludge blanket levels in primary, secondary, and tertiary settlement tanks either with stationary or traveling bridges, clarifiers, gravity thickeners, or sequencing batch reactor (SBR) systems. The two-part system includes a purpose-built self-cleaning Viper Transducer that uses sonar technology, submersed into the liquid, and detects the echoes from the material. Any distinct change in density is reflected to the transducer – the time taken for the echo to return is transmitted to the controller and the distance to the interface is calculated.
The Sludge Finder 2 offers a wealth of different options depending on the application requirements, including single or dual sensor inputs, installation accessories, communication outputs, and PC Software Suite that offers Sludge Finder 2 software that can be used to record and save all the parameters from your sludge blanket level measurement applications.
• Primary & Secondary Settlement Tanks
• DAF Thickeners
• Gravity Thickeners
• Stationary & Traveling Bridges
General Specifications | |
---|---|
Spec: | Description: |
Weight | 1 kg (2.2 lbs) |
Cable entry details | 10 cable entry knockouts, 5 x M20, and 1 x M16 underside. 4 x PG11 at rear |
Operating Temperature (Electronics) | -20 °C to +50 °C (-4 °F to +122 °F) |
Analog output | 2 x isolated (to 150 V floating) output of 4-20mA or 0-20mA into 1 kΩ (user-programmable and adjustable) 0.1% resolution |
Digital output | Half-duplex RS232 |
Display | 192 x 128 pixel illuminated graphical display showing a variety of screens including echo profile. Fully programmable display options, integral keypad with menu navigation keys |
PC Software | Sludge Finder PC within PC Software Suite - compatible with XP (service pack 3), Windows 7/8/10 |
Fuse | 2 A slow blow |
Operating Voltage | Universal 100-240 V AC 50/60 Hz, 22-28 V DC |
Power Consumption | 20 W maximum power (typically 11 W) |
Viper Sensor Specifications | |
---|---|
Spec: | Description: |
Sensor body dimensions | 78 mm x 195 mm (3.07 in x 7.67 in) |
Sensor body weight | Nominal 1.5 kg (3.3 lbs) |
Sensor body material | Valox 357 Wiper blade - Stainless steel |
Transducer cable extensions | 4-core screened |
Maximum separation | 200 m (656 ft) |
Enclosure protection | IP68 |
Accuracy | 0.25% of the measured range or 10 mm (0.39 in); whichever is greater |
Resolution | 0.25% of the measured range or 10 mm (0.39 in); whichever is greater |
Max range | 10 m (32.8 ft) |
Min range | 0.3 m (0.98 ft) |
Minimum sludge density | 0.5% concentration |
Options | |
---|---|
Option: | Description: |
Communications | Modbus Profibus communications option V1 DX80 radio transmitter |
Cable | Various cable lengths available |
Mounting | Sludge Finder 2 Cabinet Mounting Kits & Brackets available |
Approvals;
- CE Approval
- ATEX Approval (ST10 Transducer option only)