IMP+ Ultrasonic Level Transmitter
- Compact self-contained level measurement
- Calibrate without compromising the IP67 rating
- Simple menu led set-up
- High power and narrow beam angles
The IMP+ non-contacting ultrasonic sensor is designed to be used wherever you need an accurate and reliable level measurement. Its digital echo processing means the IMP+ is perfect for slurries, liquids, or anywhere you need a display telling you the level or analog output to interface with your site control system or drive a display.
There are several measurement ranges available from 0 m to 10 m and each can be wired for 2 or 3-wire operation. All options feature an LCD display and digital temperature measurement and compensation. When combined with Pulsar’s PC Suite, users are able to download, analyze and store echo profiles, set up the IMP’s parameters, install the new firmware to your IMP, and add a flow curve to be able to configure level to flow linearization.
• Tank Level Applications
• Chemical Dosing
• Simple Level Indication
• Open & Closed Vessel Level Requirements
• Solids Level Indication
Dimensions | 186 mm (H) x 133 mm (D) (5.24 in (H) x 7.32 in (D)) |
Cable Entry: | 2 off cable glands 4.5 mm to 10 mm (0.18 in to 0.39 in); Torque to 2 NM |
Mounting: | IMP3 - 3 m (10 ft) version: 1.5 in BSP/NPT IMP 6 - 6 m (20 ft) version: 1.5 in BSP/NPT IMP10 - 10 m (33 ft) version: 2 in BSP/NPT Suits BSP & NPT, parallel and tapered |
Weight | Nominal 1kg (2.2 lb) |
Enclosure Protection | IP67 |
Temperature (Process) | -4 0°C to +65 °C (-40 °F to +149 °F ) |
Temperature (Ambient) | -40 °C to +80 °C (-40 °F to +176 °F) |
Input Voltage Range | 11-30 V, 3.5-22 mA |
Accuracy | ±0.25% or 6 mm (0.24 in) whichever is greater |
Resolution | ±0.1% or 2 mm (0.08 in) whichever is greater |
4-20mA Outputs | Resolution 5 μA; both active and passive outputs |
Temperature Compensation | Via internal temperature sensor 0.5 °C (± 32.9 °F) accuracy. Level and volume conversion are installed allowing linearisation for tank shapes. |
PC Interface | All parameters can be accessed and changed through PC Suite software. Echo traces may be viewed on-screen. |
Options | |
---|---|
Option: | Description: |
Variants | IMP Lite IMP I.S. |
Configurations | 2-Wire or 3-Wire |
Beam Angle (-3 dB half power) | IMP3: ‹10° inclusive IMP6: ‹10° inclusive IMP10: ‹10° inclusive |
Operating Frequency | IMP3: 125 kHz IMP6: 75 kHz IMP10: 41 kHz |
Measurement Range | IMP3: 0.2 m to 3 m (0.66 ft to 10 ft) IMP6: 0.3 m to 6 m (0.98 ft to 20 ft) IMP10: 0.3 m to 10 m (0.98 ft to 33 ft) |
Software | IMP PC |