IMP + I.S Ultrasonic Level Sensor
- Compact and self-contained level measurement
- Simple menu led setup
- High power and narrow beam angles
- High specification ATEX
- Up to 10 m (33 ft) range available
IMP+ I.S. is part of the Pulsar Measurement IMP family, a combined transducer and controller range in one self-contained unit. The IMP+ I.S. unit is certified to ATEX standard EEx ia IIC T4 and IECEx and available with the wetted parts in PVDF, making it ideal for measuring in corrosive or aggressive applications or anywhere where you need an accurate and reliable level measurement. The IMP+ I.S. benefits from our specially designed digital echo processing technique. The IMP+ I.S. are availble in three sizes from 3 m to 10 m (10 ft to 33 ft). With the benefit of the on board LCD display and keypad the IMP+ I.S. is straight forward to set up using the menu led programming.
• Tank Level Applications
• Chemical Dosing
• Simple Level Indication
• Open & Closed Vessel Level Requirements
• Solids Level Indication
General Specifications | |
---|---|
Spec: | Description: |
Dimensions | 186 mm H x 133 mm D (5.24 in H x 7.32 in D) |
Cable Entry | 2 x cable glands 4.5 mm to 10 mm (0.18 in to 0.39 in) (Torque to 2 NM) |
Mounting | IMP3 - 3 m (10 ft) version: 1.5 in BSP/NPT IMP 6 - 6 m (20 ft) version: 1.5 in BSP/NPT IMP10 - 10 m (33 ft) version: 2 in BSP/NPT Suits BSP & NPT, parallel and tapered |
Weight | Nominal 1 kg (2.2 lb) |
Enclosure Protection | IP67 |
Temperature (Ambient) | -40 °C to +6 5 °C (-40 °F to +149 °F) |
Temperature (Process) | -40 °C to +80 °C (-40 °F to +176 °F) |
Input Voltage Range | 11-30 V, 3.5-22 mA |
Accuracy | ±0.25% or 6 mm (0.24 in); whichever is greater |
Resolution | ±0.1% or 2 mm (0.08 in); whichever is greater |
4-20mA Outputs | Resolution 5 μA (both active and passive outputs) |
Temperature Compensation | Via internal temperature sensor (0.5 °C (± 32.9 °F) accuracy). Level and volume conversion are installed allowing linearisation for tank shapes. |
PC Interface | All parameters can be accessed and changed through PC Suite software. Echo traces may be viewed on-screen. |
Options | |
---|---|
Option: | Description: |
Variants | IMP+ IMP Lite |
Configurations | 2-Wire or 3-Wire |
Beam Angle (-3 dB half power) | IMP3: ‹10° inclusive IMP6: ‹10° inclusive IMP10: ‹10° inclusive |
Operating Frequency | IMP3: 125 kHz IMP6: 75 kHz IMP10: 41 kHz |
Measurement Range | IMP3: 0.2 m to 3 m (0.66 ft to 10 ft) IMP6: 0.3 m to 6 m (0.98 ft to 20 ft) IMP10: 0.3 m to 10 m (0.98 ft to 33 ft) |
Software | IMP PC |